Home    SWITCH POWER SUPPLY    DR-15 Din rail power supply

Product Details

DR-15 Din rail power supply

 

15W Single Output Industrial DIN Rail Power Supply    DR-15 series

Features:
Universal AC input/ full range
Protections: Short circuit/ Over load/ Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation classⅡ
LED indicator for power on
100% full load burn-in test
2 year warranty

SPECIFICATIONS
OUTPUT  
Model DR-15-5 DR15-12 DR-15-15 DR-15-24
DC Voltage 5V 12V 15V 24V
Rated Current 2.4A 1.25A 1A 0.63A
Current Range 0-2.4A 0-1.25A 0-1A 0-0.63A
Rated Power 12W 15W 15W 15.2W
Ripple & Noise 80mVp-p 120mVp-p 120mVp-p 150mVp-p
Voltage Adj. Range -5%,+10% ±10% ±10% ±10%
Voltage Tolerance ±2% ±1% ±1% ±1%
Setup, Rise, Hold Up Time 1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full load70ms/230VAC          16ms/115VAC at full load
INPUT  
Voltage Range 85 ~ 264VAC          120 ~ 370VDC
AC Current 0.88A/115VAC          0.48A/230VAC
Efficiency 74% 84% 83.50% 85%
Inrush Current COLD START 35A/115VAC          65A/230VAC
PROTECTION  
Over Load 105%~160%
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage 115%~135%
Protection type: Shut down o/p voltage, re-power on to recover
ENVIRONMENT  
Working Temp., Humidity -10℃~+60℃; 20%~90%RH
Storage Temp., Humidity -40℃~+85℃; 10%~95%RH
Temp. Coefficient ±0.03%/℃(0~50℃)
Vibration 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
SAFETY  
Withstand Voltage I/P-O/P: 3KVAC
Isolation Resistance I/P-O/P: 100M Ohms / 500VDC
STANDARD  
Safety Standard Design refer to UL60950-1,TUV EN60950-1,EN50178
EMC Standard Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3
OTHERS  
Dimension 25*93*56mm(L*W*H)
Weight 0.15Kg
Packing 140pcs/carton
   
NOTE  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

15W din rail switching power supply
88~132VAC/176~264VAC selected by switch
50/60Hz